12
MAMM-WSHP-IOM-1MA
MAMMOTH CONTROLS
I/O 560
Mammoth I/O Zone 560 controller delivers powerful
control and communications features all in a compact,
economical package. Fully capable of operating in a
100% stand-alone control mode, the I/O Zone 560 can
connect to a Building Automation System (BAS) using
any of today’s most popular protocols, such as BACnet,
Modbus, N2, LonTalk. The I/O Zone 560 also supports
communication to the Mammoth line of intelligent space
sensors and keypad/display units.
Key Features and Benefits
 I/O point count: 5 digital outputs (relayed), and 6 universal imputs.
 Built-in protocol support: BACnet (ARCNET and MS/TP), Modbus RTU, and N2. Optional plug-in communica-
tions boards: LonTalk
 On-board battery-backed real-time clock is standard, thus enabling full stand-alone scheduling capabilities as
well as historical trend data storage and alarm event time-stamping.•
 Powerful, high-speed 16-bit processor with 1MB Flash memory and 512KB of battery-backed RAM - plenty of
room for even demanding and complex applications.
 For standard CAV heat pumps without modulating waterside economizer (WSE) or hot gas
Reheat (HGR).
 For variable air volume (VAV), constant volume (CAV), and make-up air (MAU) applications.